Insulation Facing Technical Data

  • Insulation Facing Properties:

    Physical properties Test Method Value (English) Value (Metric)
    Basis weight Scale 14.8 lbs / 1000 ft2 72.5 gsm
    Permeance (WVTR) ASTM E96,
    Procedure A
    0.02 perm 1.15 ng/N.s
    Tensile Strength-MD ASTM D828 16 lbs / In 70 N/25mm
    Tensile Strength-XD ASTM D828 15.5 lbs / In 68 N/25mm
    Burst Strength ASTM D774 50.4psi 35 N/cm2
    Low temperature
    Resistance
    ASTM D1790
    4 hrs @
    -40℉ (-40℃)
    Remains Flexible
    No Delamination
    Remains Flexible
    No Delamination
    High temperature
    Resistance
    ASTM D1790
    4 hrs @
    +240℉ (+116℃)
    Remains Flexible
    No Delamination
    Remains Flexible
    No Delamination
    Emissivity ASTM E408 -0.05 -0.05
  • Facing construction:

    Composition Description Value (English) Value (Metric)
    Foil Aluminum 0.60 mil 15 micron
    Reinforcing- MD Fiberglass 1/5 inch spacing 5mm spacing
    Reinforcing-XD Fiberglass 1/5 inch spacing 5mm spacing
    Heat-Activated Adhesive Polyethylene 1 mil 25 micron

FAQ:

  1. Q1: What is FSK Foil Faced Insulation made of?

    A: FSK Foil Faced Insulation is composed of a 15u aluminum foil laminated to a 2-way fiberglass scrim (5x5mm spacing) with a heat-activated polyethylene backing.

  2. Q2: What are the primary benefits of using fsk insulation?

    A: It provides superior abrasion resistance, enhances energy efficiency by reducing heat loss, acts as a dual thermal and moisture barrier, and offers lightweight flexibility for easy installation.

  3. Q3: Can fsk faced insulation be used in HVAC ductwork?

    A: Yes, it is ideal for insulating HVAC ductwork to help reduce heat loss, control temperature, and provide essential vapor protection.

  4. Q4: Is foil scrim kraft insulation suitable for metal buildings?

    A: Yes, it is widely used for insulating metal buildings where effective heat reflection and moisture control are critical for maintaining stable internal temperatures.